In normal operation, the secondary winding of the CT must remain closed through a burden circuit, or short circuit. The leads of the secondary winding may only be opened during an inter-turn over voltage test. The test current at system frequency in the primary winding must be no more than the rated current, and the peak induced voltage between the leads of the secondary winding must be no more than 4.5 kV for 60 sec. The voltage may be measured and recorded by a high impedance measurement device connected to the leads of the secondary winding.
In the event of the CT’s secondary winding circuit being opened, due to a protection relay failure or any other reason, a no-load condition exists on the secondary winding circuit. As a result, the CT behaves like a current generator connected to a high impedance load, or open circuit. Consequently, the CT behaves like an ignition coil, producing extremely high voltages. This is a hazard that, in rare circumstances, has resulted in fatalities.
Partial discharge is most likely to occur in the oil insulation between the secondary winding leads, between these leads and the tank, and in one of the bushings between the turns on the winding. The level of partial discharge is dependent on the amplitude of the induced voltage.
Monday, May 24, 2021
Current transformer (CT) can cause serious damage
Subscribe to:
Post Comments (Atom)
Multiple opportunities to monetize your skills and time.
E arn Money Online Every Day! Multiple opportunities to monetize your skills and time. _Popular Ways to Earn Money Online:_ 1. _Freelanci...
-
৩৩ কেভি লাইন চালু ও বন্ধ করার পদ্ধতি- ৩৩ কেভি লাইন চালু করার পদ্ধতি- ১। সঠিকভাবে লাইন ক্লিয়ারেন্স (ফিডার সুপারভাইজার/ইনচার্জ/ফোরম্যান/লাইনম...
-
E arn Money Online Every Day! Multiple opportunities to monetize your skills and time. _Popular Ways to Earn Money Online:_ 1. _Freelanci...
-
Bay Hills Hotel: A Gem at Himchari, Cox's Bazar,Bangladesh Nestled along the stunning coastline of Cox Bazar, Bangladesh, the Bay Hills...

No comments:
Post a Comment